Monitoring APC UPS – Useful OIDs
Battery capacity
1.3.6.1.4.1.318.1.1.1.2.2.1.0
Value type Gauge Float
Division = 1
Value %
Run Time Remaining
1.3.6.1.4.1.318.1.1.1.2.2.3.0
Value type Gauge Integer
Division = 6000
Value minutes
Battery Temperature
1.3.6.1.4.1.318.1.1.1.2.3.2.0
Value type Gauge Float
Division = 10
Value °
Battery Actual Voltage
1.3.6.1.4.1.318.1.1.1.2.3.4.0
Value type Gauge Float
Division = 10
Value VDC
Input Line Voltage
1.3.6.1.4.1.318.1.1.1.3.3.1.0
Value type Gauge Float
Division = 10
Value VAC
Output Voltage
1.3.6.1.4.1.318.1.1.1.4.3.1.0
Value type Gauge Float
Division = 10
Value VAC
Output Load
1.3.6.1.4.1.318.1.1.1.4.3.3.0
Value type Gauge Integer
Division = 10
Value %
Input Frequency
1.3.6.1.4.1.318.1.1.1.3.3.4.0
Value type Gauge Integer
Division = 10
Value Hz
Output Frequency
1.3.6.1.4.1.318.1.1.1.4.3.2.0
Value type Gauge Integer
Division = 10
Value Hz
Last Battery Test Status
1.3.6.1.4.1.318.1.1.1.7.2.3.0
Division = 1
Value #
Set Value lookup on channel
Battery replace
1.3.6.1.4.1.318.1.1.1.2.2.4.0
Division = 1
Value #
Set Value lookup on channel
Monitoring APC UPS – Useful OIDs
If you feel moved to monitor your APC UPS, here are some of the OIDs you'll want to use. These OIDs definitely work with the APC AP9617 management card which plugs in the back of APC devices.
General
UPS Type .1.3.6.1.4.1.318.1.1.1.1.1.1.0
String containing UPS model, eg: Smart-UPS 1000
Battery Information
Battery capacity .1.3.6.1.4.1.318.1.1.1.2.2.1.0
Battery capacity as % of total
Battery temperature .1.3.6.1.4.1.318.1.1.1.2.2.2.0
Battery temperature in Celcius of Farenheit – depending on how UPS is configured
Battery runtime remain .1.3.6.1.4.1.318.1.1.1.2.2.3.0
Total battery runtime available based on current load.
Battery replace .1.3.6.1.4.1.318.1.1.1.2.2.4.0
If result = 2 then battery needs replacing (1 = ok)
UPS Input
Input voltage .1.3.6.1.4.1.318.1.1.1.3.2.1.0
Input voltage, to the UPS device
Input frequency .1.3.6.1.4.1.318.1.1.1.3.2.4.0
Input frequency in Hz
Reason for last transfer .1.3.6.1.4.1.318.1.1.1.3.2.5.0
String containing reason for last transfer to battery power
1 No events
2 High line voltage
3 Brownout
4 Loss of mains power
5 Small temporary power drop
6 Large temporary power drop
7 Small spike
8 Large spike
9 UPS self test
10 Excessive input voltage fluctuation
UPS Output
Output voltage .1.3.6.1.4.1.318.1.1.1.4.2.1.0
Output voltage from the UPS
Output frequency .1.3.6.1.4.1.318.1.1.1.4.2.2.0
Output frequency in Hz
Output load .1.3.6.1.4.1.318.1.1.1.4.2.3.0
Output load expressed as % of capacity
Output current .1.3.6.1.4.1.318.1.1.1.4.2.4.0
Output current in Amps
Diagnostics
Comms .1.3.6.1.4.1.318.1.1.1.8.1.0
Whether SNMP agent is communicating with UPS device 1 = yes, 2 = no
Last Self Test result .1.3.6.1.4.1.318.1.1.1.7.2.3.0
Result of last self test as text string. eg: pass or fail.
Last Self Test date .1.3.6.1.4.1.318.1.1.1.7.2.4.0
Date of last self test